Communication Description
IM/265/7/9/ADD/FF-EN_01
Series 2600T Pressure Transmitters
Connection to FOUNDATION Fieldbus
For pressure, differential pressure, level, and
pressure/temperature-corrected flow measurement
Communication description for
FOUNDATION Fieldbus
- Valid for models 265Dx, 265VS, 265Gx, 265Ax,
267JS, 267Cx, 269JS, 269Cx
Zobrazit stránku 0
1 2 3 4 5 6 ... 81 82

Shrnutí obsahu

Strany 1 - Communication Description

Communication Description IM/265/7/9/ADD/FF-EN_01 Series 2600T Pressure TransmittersConnection to FOUNDATION Fieldbus For pressure, differential

Strany 2

Device Introduction 10 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01

Strany 3

Device Introduction IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 11 - DEVICE Model: 2600T Series- Models 267 / 269 Type: Multivari

Strany 4

Device Introduction 12 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01

Strany 5 - 4 Device Introduction

Hardware Characteristics IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 13 5 Hardware Characteristics 5.1 Current limitation This

Strany 6

Hardware Characteristics 14 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 5.3 Local Keys Three external push buttons are availabl

Strany 7 - Device Introduction

Hardware Characteristics IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 15 5.4 Structure tree The menu is called up using the mode

Strany 8

Hardware Characteristics 16 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 Main menu Submenu (other parameters / explanations)

Strany 9

Network Architecture IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 17 6 Network Architecture A simple generic FOUNDATIONTM Fieldbus

Strany 10 - Device Introduction

Network Architecture 18 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 M00506Trunk & Spurs Daisy Chain TreeJunction Box Fig. 4: F

Strany 11

Network Architecture IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 19 The models 265 / 267 / 269 FF have the following power requireme

Strany 12

Blinder Text 2 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 Series 2600T Pressure Transmitters Connection to FOUNDATION Fieldbus

Strany 13 - 5 Hardware Characteristics

Network Architecture 20 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 6.1 Electrical Connections The 2600 FF is a Bus Powered dev

Strany 14 - Hardware Characteristics

FOUNDATION Fieldbus Overview IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 21 Approvals 7 FOUNDATION Fieldbus Overview In the Fig.

Strany 15

FOUNDATION Fieldbus Overview 22 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 In the Fig. 8 is represented the macro cycle of the abo

Strany 16

Initialisation IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 23 8 Initialisation At the power up, the 2600T FF executes some inter

Strany 17 - Pressure Tx

Device Addressing 24 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 A 9 Device Addressing When the models 265 / 267 / 269 FF Transmi

Strany 18 - Junction Box

Device Configuration IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 25 K 10 Device Configuration 10.1 Device Description The model

Strany 19 - Network Architecture

Device Configuration 26 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 10.2 Resource Block Idx Name Byte PC Description 0 BLO

Strany 20 - Network Architecture

Device Configuration IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 27 Idx Name Byte PC Description 1 R/W Grant 14 GRANT_DENY 1

Strany 21 - AO execution

Device Configuration 28 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 Idx Name Byte PC Description 26 SHED_RCAS 4 R/W Time du

Strany 22 - Netw ork

Device Configuration IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 29 Idx Name Byte PC Description The alert status associated to

Strany 23

Preamble IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 3 1 Preamble ...

Strany 24 - 9 Device Addressing

Device Configuration 30 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 Idx Name Byte PC Description 46 DIAGNOSIS 4 R Diagnosis

Strany 25 - 10 Device Configuration

Device Configuration IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 31 Idx Name Byte PC Description 48 DIAGNOSIS_ EXTENSION2 2 R

Strany 26

Device Configuration 32 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 10.3 Analog Input Function Block Idx Name Byte PC Descr

Strany 27

Device Configuration IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 33 Idx Name Byte PC Description 4 R/W High Range 4 R/W Low Rang

Strany 28

Device Configuration 34 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 Idx Name Byte PC Description Code for Flow 1347 cubic me

Strany 29

Device Configuration IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 35 Idx Name Byte PC Description Code for Volume 1034 cubic

Strany 30

Device Configuration 36 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 Idx Name Byte PC Description 17 LOW_CUT 4 R/W Limit use

Strany 31

Device Configuration IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 37 Idx Name Byte PC Description The block alarm is used for a

Strany 32 - Device Configuration

Device Configuration 38 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 Idx Name Byte PC Description The HI HI Alarm data 1 R/W U

Strany 33

Device Configuration IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 39 10.4 Pressure Transducer Block The modification of the flow

Strany 34

Preamble 4 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 1 Preamble In order to make easier the description, all the variables menti

Strany 35

Device Configuration 40 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 Idx Name Byte PC Description The block alarm is used for

Strany 36

Device Configuration IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 41 Idx Name Byte PC Description 4 R This is the output value

Strany 37

Device Configuration 42 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 Idx Name Byte PC Description 26 SENS_CAL_WHO 32 R/W The

Strany 38

Device Configuration IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 43 Idx Name Byte PC Description Type of Process connection: 36

Strany 39

Device Configuration 44 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 Idx Name Byte PC Description Number of remote seals: 40 NUM

Strany 40

Device Configuration IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 45 Idx Name Byte PC Description Linearization type: 51 LIN_TYPE

Strany 41

Device Configuration 46 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 Idx Name Byte PC Description 58 TAB_OP_CODE 1 58 Modifi

Strany 42

Device Configuration IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 47 Idx Name Byte PC Description 72 UPPER_RANGE_ FAILURE 1 R/W

Strany 43

Device Configuration 48 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 10.5 PID Function Block Idx Name Byte PC Description 0

Strany 44

Device Configuration IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 49 Idx Name Byte PC Description 4 R/W High Range 4 R/W Low Rang

Strany 45

FOUNDATION Fieldbus Definition IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 5 3 FOUNDATION Fieldbus Definition FOUNDATION™ Field

Strany 46

Device Configuration 50 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 Idx Name Byte PC Description 4 R/W Remote set point value

Strany 47

Device Configuration IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 51 Idx Name Byte PC Description 4 R The value required by an

Strany 48

Device Configuration 52 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 Idx Name Byte PC Description 4 R/W This input is used as

Strany 49

Device Configuration IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 53 Idx Name Byte PC Description The summary alarm is used for

Strany 50

Device Configuration 54 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 Idx Name Byte PC Description 58 DV_LO_PRI 1 R/W The Pri

Strany 51

Device Configuration IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 55 Idx Name Byte PC Description Low Low Alarm data 1 R/W Unac

Strany 52

Device Configuration 56 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 10.6 Temperature Transducer Block (only 267 / 269 transmitter

Strany 53

Device Configuration IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 57 Idx Name Byte PC Description The block alarm is used for a

Strany 54

Device Configuration 58 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 Idx Name Byte PC Description 16 CAL_POINT_HI 4 R/W The

Strany 55

Device Configuration IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 59 10.7 Multi Variable Block (only 267C / 269C transmitters) Th

Strany 56

Device Introduction 6 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 4.2 FOUNDATIONTM Fieldbus Version Considerations The models

Strany 57

Device Configuration 60 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 Idx Name Byte PC Description 12 PRESSURE_DEFAULT 4 R Pre

Strany 58

Device Configuration IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 61 Idx Name Byte PC Description 22 SIMULATE_ PRESSURE 1 R/? S

Strany 59

Device Configuration 62 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 Idx Name Byte PC Description The block alarm is used for

Strany 60

Device Configuration IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 63 Idx Name Byte PC Description 36 OUT_MASS_FLOW_ MAX 4 R Max

Strany 61

Operating Modes 64 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 11 Operating Modes As defined by the FOUNDATIONTM Fieldbus specif

Strany 62

Process Flow IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 65 12 Process Flow The following Figures show the possible connections

Strany 63

Process Flow 66 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 M00515BlockPressureTransducer2MVTemp.VOLAnalog1InputTemp.MediumOUTAnalo

Strany 64

Process Flow IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 67 12.2 Custom Pressure Transducer Block M00516Output ScalingSTATIC_PR

Strany 65 - 12 Process Flow

Process Flow 68 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 12.4 PID Function Block M00518ScalingwithLimitingwithOUT_HI_LIMOUT_

Strany 66 - Process Flow

Process Flow IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 69 12.5 PID algorithm M00519FF_deviationif FF.status(k-1) = GOOD and F

Strany 67

Device Introduction IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 7 - LAS Functionality With this functionality the models 265 / 26

Strany 68

Process Flow 70 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 12.6 Custom Temperature Transducer Block M00520SensorTemperatureTem

Strany 69

Process Flow IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 71 12.8 Troubleshooting Few considerations about the most common wrong

Strany 70

Process Flow 72 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 12.9 Status supported The FOUNDATION™ Fieldbus defines different dy

Strany 71

Process Flow IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 73 Configuration error detail: Set if the AIFB Channel is different by 0 b

Strany 72

Process Flow 74 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 Details for UNCERTAIN 68 44 0 1 0 0 0 1 = Last Usable Value TB 72 4

Strany 73

Process Flow IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 75 Details for GOOD (non-cascade) 128 80 1 0 0 0 0 0 = ok TB, AI, MV,

Strany 74

Process Flow 76 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 Details for GOOD (cascade) 192 C0 1 1 0 0 0 0 = ok PID 196 C4 1 1

Strany 75

Process Flow IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 77 Details for bits 'LIMITS' +0 +00 0 0 = ok +1 +01

Strany 76

Device Specification Data 78 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 13 Device Specification Data The delivery of the model

Strany 77

Device Specification Data IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 79 The following table is a summary of the most important mod

Strany 78 - Device Specification Data

Device Introduction 8 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 - FMS services supported: - Initiate - Abort - Status - Id

Strany 79 - Device Specification Data

Reference 80 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01 K 14 Reference 1. Function Block Application Process – Part 2. n° FF-

Strany 81

ABB has Sales & Customer Support expertise in over 100 countries worldwide. www.abb.com/pressure The Company’s policy is one of continuou

Strany 82

Device Introduction IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 9 4.3 Registration Details - DEVICE Model: 2600T Series- Model